Two-Way Slab Calculator

Design two-way reinforced concrete flat plate slabs using the Direct Design Method per ACI 318.

Panel Parameters

Span Ratio

1.25

Two-way action governs

Thickness OK (min: 7.27")

Total Static Moment (Mo)

Long Direction

179.20 k-ft

Short Direction

143.36 k-ft

Column Strip Moments (k-ft/ft)

Long: -M interior

11.760

Long: +M midspan

4.704

Short: -M interior

9.408

Short: +M midspan

3.763

Required Reinforcement

Long Direction

0.402 in²/ft

#4 @ 6.0" o.c.

Short Direction

0.310 in²/ft

#4 @ 7.7" o.c.

Column strip width: 8.0 ft
Factored load: 224.0 psf

Direct Design Method Requirements

DDM Applicability

  • Minimum 3 continuous spans each direction
  • Span ratio (long/short) ≤ 2
  • Successive spans differ by ≤ 1/3
  • Columns offset ≤ 10% of span
  • Uniform loading, LL/DL ≤ 2

Moment Distribution

  • Interior negative: 65-70% of Mo
  • Positive: 35-52% of Mo
  • Column strip: 60-75% of panel moment
  • Middle strip: remainder